Transformers are among the most efficient electrical machines ever engineered, typically achieving efficiencies between 98% and 99.5%. However, because distribution and power transformers remain energized 24 hours a day, 365 days a year across thousands of grid substations, even a fraction of a percent of wasted energy translates into substantial financial cost, thermal stress, and carbon emissions. Accurately calculating and testing Transformer Losses is therefore vital for utilities, industrial plant owners, and electrical design engineers.
Main Categories of Transformer Losses
Total active power loss in a transformer is divided into two fundamental categories:
- No-Load Losses (Core / Iron Losses — P₀): Constant losses occurring in the magnetic silicon-steel core whenever the transformer is energized at rated voltage and frequency, regardless of whether any load is connected to the secondary terminals.
- Load Losses (Copper / Winding & Stray Losses — Pₖ): Variable losses that occur in the primary and secondary windings as load current flows through them, increasing proportionally to the square of the load current (I²).

1. How to Calculate Constant (No-Load) Losses: Hysteresis & Eddy Currents
No-load core loss is the sum of Hysteresis Loss (energy consumed by continuous reversal of magnetic domains in the core steel) and Eddy Current (Foucault) Loss (circulating currents induced within conductive core laminations by alternating magnetic flux).
Measurement via Open-Circuit Test (IEC 60076-1):
With the high-voltage (HV) winding left open-circuited (no load connected), rated nominal voltage at rated frequency (50 Hz) is applied to the low-voltage (LV) winding. A precision low-power-factor wattmeter connected in the supply circuit measures the active input power. Because the no-load excitation current is very small (typically 0.5% to 2% of rated current), winding I²R loss during this test is negligible, and the wattmeter reading directly equals the Total No-Load Core Loss (P₀).
In factory design optimization, engineers separate hysteresis and eddy current components using theoretical Steinmetz formulas to select thinner CRGO laminations (e.g., 0.23 mm) and higher-permeability steel grades.
2. How to Calculate Variable (Load) Losses: Ohmic (I²R) & Stray Eddy Losses
Load losses occur only when load current flows through the transformer windings and consist of:
- DC Ohmic (Copper/Aluminum) Loss: Calculated directly from conductor resistance and current:
Pohmic = R × I²
- Winding Eddy Current & Stray Load Losses: Caused by alternating leakage magnetic flux inducing eddy currents inside winding conductors, core clamps, and tank walls (typically accounting for an additional 5% to 50% above pure DC ohmic loss at higher frequencies or harmonic loads).
Measurement via Short-Circuit Test (IEC 60076-1):
With the low-voltage (LV) terminals bolted in a solid short circuit, a variable reduced voltage (typically 4% to 8% of rated voltage—the impedance voltage Uk%) is applied to the high-voltage (HV) winding until exact rated nominal current flows through the windings. Because the applied voltage is only a small fraction of nominal voltage, core flux density and core loss during this test are negligible, and the wattmeter reading (corrected to reference temperature, e.g., 75°C) equals the Total Rated Load Loss (Pₖ).
Summary
Evaluating both no-load losses (P₀) and load losses (Pₖ) via standardized Open-Circuit and Short-Circuit tests enables utilities and industrial buyers to verify transformer efficiency, calculate total lifecycle energy costs, and select low-loss transformers that deliver decades of economical, environmentally sustainable operation.