Niroo Transfo Manufacturing Co.
Buchholz Protection Relay
Certified Transformer Component

Buchholz Protection Relay

By detecting internal faults in the transformer and issuing alarm or trip signals, the Buchholz relay protects the transformer against hazards arising under the following conditions:
1. Gas accumulation caused by the decomposition of insulating oil or solid insulation due to active-part faults.
2. Drop in oil level resulting from leakage in the transformer tank.
3. Rapid oil surge from the main tank toward the conservator caused by sudden oil expansion during an internal short circuit.
When an incipient fault occurs inside the transformer, evolved gas bubbles rise toward the conservator and collect inside the Buchholz relay chamber. This gas accumulation displaces oil and lowers the oil level in the chamber, actuating the upper float contact to trigger an Alarm signal.
If fault gas generation continues and the oil level drops further, the lower float is actuated and its contact issues a Trip command to disconnect the transformer from the power supply. During a severe internal short circuit causing an abnormal high-velocity oil surge toward the conservator, the surge flap linked to the lower assembly immediately actuates the trip contact.