Niroo Transfo Manufacturing Co.
250 kVA Low-Loss Oil-Immersed Distribution Transformer
250 kVA — 20/0.4 kVTavanir Approved Low-Loss

250 kVA Low-Loss Oil-Immersed Distribution Transformer

Three-phase 250 kVA low-loss oil-immersed distribution transformer (Dyn5) engineered and manufactured by Niroo Transfo in compliance with IEC 60076 and Tavanir utility standards.

Vector GroupDyn5
CoolingONAN
No-Load Loss530 W
Load Loss3250 W

Electrical & Technical Specifications — 250 kVA Low-Loss Transformer

Rated Power (kVA)250 kVA
Rated Primary Voltage (V)20000 V
Rated Secondary Voltage (V)400 V
Voltage Tapping Range (%)±2×2.5%
Rated Frequency (Hz)50 Hz
Vector GroupDyn5
Short-Circuit Impedance (%)4%
Cooling ClassONAN
Rated Primary Current (A)7.22 A
Rated Secondary Current (A)360.84 A
No-Load Loss P0 (W)530 W
Load Loss Pk at 75°C (W)3250 W
Max Ambient Temperature (°C)45 °C
Installation Altitude (m)≤ 1000 m
Insulation Test Voltage Pri/Sec (kV)50/3 kV

Dimensional Outline & Mechanical Drawing

250 kVA Transformer Outline Drawing