Niroo Transfo Manufacturing Co.
315 kVA Low-Loss Oil-Immersed Distribution Transformer
315 kVA — 20/0.4 kVTavanir Approved Low-Loss

315 kVA Low-Loss Oil-Immersed Distribution Transformer

Three-phase 315 kVA low-loss oil-immersed distribution transformer (Dyn5) engineered and manufactured by Niroo Transfo in compliance with IEC 60076 and Tavanir utility standards.

Vector GroupDyn5
CoolingONAN
No-Load Loss625 W
Load Loss3900 W

Electrical & Technical Specifications — 315 kVA Low-Loss Transformer

Rated Power (kVA)315 kVA
Rated Primary Voltage (V)20000 V
Rated Secondary Voltage (V)400 V
Voltage Tapping Range (%)±2×2.5%
Rated Frequency (Hz)50 Hz
Vector GroupDyn5
Short-Circuit Impedance (%)4%
Cooling ClassONAN
Rated Primary Current (A)9.09 A
Rated Secondary Current (A)454.66 A
No-Load Loss P0 (W)625 W
Load Loss Pk at 75°C (W)3900 W
Max Ambient Temperature (°C)45 °C
Installation Altitude (m)≤ 1000 m
Insulation Test Voltage Pri/Sec (kV)50/3 kV

Dimensional Outline & Mechanical Drawing

315 kVA Transformer Outline Drawing